Operating instructions i550 cabinet frequency inverter | 43
© 11/2021 · EN · www.Lenze.com
Troubleshooting
Error message
If an error is pending, the keypad shows the following information.
MAN AUTO SETLOC REM
Warn.DC Bus UV
O 1 W 3 2 2 1
1
2 3
1 = Error text
2 = Error type (F = fault, T = trouble, W = warning)
3 = Error code (hexadecimal)
Faults (F) and trouble (T) are displayed continuously. The inverter is disabled.
Warnings (W) are displayed every 2 seconds for a short time. The inverter is probably
disabled.
Reset error via keypad
Errors can be reset via the stop key.
Prerequisite: Cause of error has been eliminated and no blocking time is active.
Press the stop key to reset the error. The motor is stopped.
Press the start key to cancel the stop.
Reset error via terminal control
When terminal control is used, errors can be reset in two ways:
1. Via start signal P400.02 (default setting of digital input 1).
Prerequisite: Cause of error has been eliminated and no blocking time is active.
The signal at the digital input 1 must drop and then be applied again.
2. Via error reset signal (P400.04, default setting of digital input 2).
Prerequisite: Cause of error has been eliminated and no blocking time is active.
The error is reset if a signal is applied to digital input 2.