Operating instructions i550 cabinet frequency inverter | 45
© 11/2021 · EN · www.Lenze.com
Error code Description Classication Remedy Blocking time [s]
6280 Trigger/functions connected incorrectly Trouble
Check and correct the assignment of the triggers to the functions.
With keypad or network control, the two functions “Inverter enable” (P400.01) and “Run” (P400.02) can also
be set to “Constant TRUE [1]” to start the motor.
0
7180 Motor overcurrent Trouble
Check motor load.
Check drive dimensions.
Adapt the set error threshold (P353.01).
1
9080 Keypad removed Trouble Connect the keypad again or activate another control source. 0
FF02 Error: Brake resistor overload Trouble
Check drive dimensions.
Check settings for the brake energy management.
Note! The error will be reset if the thermal load falls below the error threshold (P707.09) of - 20%.
5
FF06 Motor overspeed Trouble Adapt the maximum motor speed (P322.00) and the error threshold (P350.01). 1
FF36 Warning: Brake resistor overload Warning
Check drive dimensions.
Check settings for the brake energy management.
Note! The warning will be reset if the thermal load falls below the warning threshold (P707.08) of - 20%.
0
FF37 Automatic start disabled Trouble Deactivate start command and reset error. 0
FF85 Keypad full control active Warning Press the CTRL key to exit control mode. 0