10
UL_Warn_p300
Lenze ¯ MA_p300 ¯ 7.0
Approval (only standard version/without PROFINET)
Underwriter Laboratories (UL), UL 61010−2−201 and CSA C22.2 No. 61010−2−201 (UL File
Number E236341)
Ratings 10.9 cm (4.3") 17.8 cm (7.0") 26.4 cm (10.4")
Input 24 V DC (±25 %), I
max
: 1.3 A 1.2 A 1.4 A
Max. surrounding air temperature at relative humidity
1)
of 40 %
Mounting position
horizontal or vertical
display on top
50 °C
45 °C
50 °C
45 °C
50 °C
50 °C
Max. surrounding air temperature at relative humidity
1)
of 90 %
All mounting positions 40 °C 30 °C 40 °C
1)
The relative humidity is linearly increasing.
J Warnings!
Field Wiring Markings
Wiring terminal: Voltage supply (24 V DC)
ƒ Use 60/75 °C or 75 °C copper wire only.
ƒ AWG 22 ... 14 (0.5 ... 2.5 mm
2
), for UL 508A min. AWG 14 (2.5 mm
2
)
ƒ Torque 5 ... 7 lb−in (0.5 ... 0.6 Nm)
Device
ƒ For use in a pollution degree 2.
ƒ This device is intended for mounting in an enclosure type 1, 2, 4 or 4X
(altitude up to 2000 m, min. surrounding air temperature 0 °C).
– Type 1 models (front panel only, indoor use only):
Panel mounted equipment, for use on a flat surface of an enclosure
type 1.
– Type 4X models (front panel only, indoor use only):
Panel mounted equipment, for use on a flat surface of an enclosure type
1, 2, 4 or 4X.
– See type key (^ 2) for the model.
ƒ Use this product only in the manner described in this manual. If the
equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
Fieldbus interfaces / Optional filedbus module (MC−Card)
ƒ Use only together with appropriate cable connectors, provided with screws
for securement and secure connector to avoid loosening.