15
Commissioning
Code Possible Settings
IMPORTANT
No. Name Lenze Selection
C34
Configuration -
analog input
0 0 0...10 V
1 0...5 V
2 0...20 mA
3 4...20 mA
C36
Voltage - DC
injection brake
(DCB)
4.0 0.0 {%} 50.0 • See CE1...CE3 and c06
• Confirm motor suitability for use with
DC braking
C37
Fixed setpoint 1
(JOG 1)
20.0 0.0 {Hz} 240
C38
Fixed setpoint 2
(JOG 2)
30.0 0.0 {Hz} 240
C39
Fixed setpoint 3
(JOG 3)
40.0 0.0 {Hz} 240
C46
Frequency setpoint 0.0 {Hz} 240 Display: Setpoint via CANopen, analog
input, or function UP/DOWN
C50
Output frequency 0.0 {Hz} 240 Display
C53
DC bus voltage 0.0 {%} 255 Display
C54
Motor current 0.0 {%} 255 Display
C87
Motor rated speed 1390 300 {RPM} 65000 Set to motor nameplate speed
C89
Motor rated
frequency
50 10 {Hz} 1000 Set to motor nameplate frequency
C90
Input voltage
selection
0 Auto Automatically sets to Low (1) or High
(2) upon next power-up, depending on
input voltage
1 Low For 200 V or 400 V input
2 High For 240 V or 480 V input
Note
• To simplify commissioning, the Lenze setting is preset at the factory, depending
on model:
C90 = 1 for 400/480 V models
C90 = 2 for 230/240 V models
• Upon reset (C02 = 1, 2), C90 = 0. Confirm correct setting after next power-up.
C94
User password 0 0 999
Changing from “0” (no password), value
will start at 763
When set to a value other than 0,
must enter password at C00 to access
parameters
C99
Software version Display, format: x.yz
c06
Holding time -
automatic DC
injection brake
(Auto-DCB)
0.0 0.0 {s} 999
0.0 = not active
999 = continuous brake
• Automatic motor braking below 0.1 Hz
by means of motor DC current for the
entire holding time (afterwards: U, V,
W inhibited)
• Confirm motor suitability for use with
DC braking
c08
Analog output
scaling
100 1.0 999 When 10 VDC is output at terminal 62, it
will equal this value (see c11)