17
Commissioning
Code Possible Settings
IMPORTANT
No. Name Lenze Selection
c78
Operating time
counter
Display
Total time in status “Start”
0...999 h: format xxx
1000...9999 h: format x.xx (x1000)
10000...99999 h: format xx.x (x1000)
c79
Mains connection
time counter
Display
Total time of mains = on
CANopen / System bus parameters
h42
Guard time 0 0 {ms} 65535 h42 x h43 = node life time
If RTR frame with ID = 0x700 + Node
ID (h50) is not received during the
node life time, the controller will react
according to h44
If heart beat message is enabled, the
guard function is disabled
h44 is only active when C01 = 3 and
h42 x h43 > 0
h43
Life time factor 0 0 255
h44
Guard time event
reaction
0 0 Not active
1 Inhibit
2 Quick stop
3 Trip fault
FC3
h45
Error behavior 1
0 transition to pre-operational
(only if current state is operational)
Specifies action taken by the drive when
it encounters a communication error
(ex. Node guarding event or Bus Off)
1 No state change
2 transition to stopped
h46
Message monitoring
time
0 0 {ms} 65535 h46 and h47 can be used to monitor
all valid messages (e.g. SDO, SYNC,
PDO...)
h46 = 0 or h47 = 0 disables message
monitoring function
h47 is only active when C01 = 3
h47
Message monitoring
time out reaction
0 0 Not active
1 Inhibit
2 Quick stop
3 Trip fault
FC3
h48
Monitoring timeout
status
Bits:
Read-only
Indicates cause of FC3 fault, inhibit, or
quick stop (depending on the settings
of h44, h47, h65, h75)
0 Guard time timeout
1 No valid message received
2 RPD01 timeout
3 RPD02 timeout
4 CAN initialization fault
5 reserved
Bits 5…7 create a binary number from 0
to 7 indicating the number of overflows in
the receive buffers (h49 bits 6 and 7)
6 reserved
7 reserved