22
Commissioning
Code Possible Settings
IMPORTANT
No. Name Lenze Selection
h96
(1)
TPDO#2 mapping
(see TPDO mapping
details)
0 0 C0150 + C50 signed C50 scaling: + 50 = + 1.0 Hz
1 C0150 + C50 unsigned C50 scaling: 10 = 1.0 Hz
2 Controller status in C0135 format +
frequency setpoint signed
Can be used to control other controllers
(see example in section 4.5)
3 Controller status in C0135 format +
frequency setpoint unsigned
4 402 Device profile: Statusword
0x6041
5 402 Device profile: Statusword
0x6041 + vl control effort 0x6044
vl control effort units = signed RPM
RPM calculation based on C87 and C89
6 C0150 + C50 signed and scaled +
digital input + analog input
C50 scaling: +/- 16384 = C11
h97
TPDO#2 WORD0
bit mask
65535 0 65535 COS (change of state) bit mask
applied to WORD0 of TPDO selected
by h96.
h97 = 65535: activates all bits of
WORD0 for COS triggering
h97 = 0: disables COS triggering
h99
TPDO#2 status 0 255 Read-only
Number of transmitted TPDO#2
messages
Above 255, starts over at 0
n20
Power up state 0 0 Quick stop Selects controller power up state when
C01 = 3 (CANopen control)
1 Inhibit
(1)
These parameters take effect only after power-up, h58 reset, “NMT reset node”, or “NMT reset communication services”