28
Commissioning
WORD0 - Statusword 0x6041
Bit h86 / h96 setting = 4
WORD0- Statusword 0x6041
Bit h86 / h96 setting = 5
0
0 = Not ready to switch on
1 = Ready to switch on
0
0 = Not ready to switch on
1 = Ready to switch on
1
0 = Not switched on
1 = Switched on
1
0 = Not switched on
1 = Switched on
2
0 = operation disabled
1 = operation enabled
2
0 = operation disabled
1 = operation enabled
3
0 = No fault
1 = Fault
3
0 = No fault
1 = Fault
4
0 = Voltage disabled
1 = Voltage enabled
Note: On smd controller, this is
always enabled
4
0 = Voltage disabled
1 = Voltage enabled
Note: On smd controller, this is
always enabled
5
0 = Quick stop active
1 = Quick stop not active
5
0 = Quick stop active
1 = Quick stop not active
6
Switch on disabled
On smd controller this is always 0
(switch on enabled)
6
Switch on disabled
On smd controller this is always 0
(switch on enabled)
7
0 = No warning
1= Warning
7
0 = No warning
1= Warning
8 Manufacturer specific 8 Manufacturer specific
9
Remote
0 = C01 < > 2 and 3
1 = C01 = 2 or 3
9
Remote
0 = C01 < > 2 and 3
1 = C01 = 2 or 3
10
Target reached
0 = Setpoint not reached
1 = Setpoint reached
10
Target reached
0 = Setpoint not reached
1 = Setpoint reached
11
Internal limit
0 = Internal limit not active
1 = Internal limit active
11
Internal limit
0 = Internal limit not active
1 = Internal limit active
12 reserved 12 reserved
13 reserved 13 reserved
14 reserved 14 reserved
15 reserved 15 reserved
WORD1
Signed output frequency read from C50
RPM is calculated based on C50, C87, and C89
Example 1 (C87 = 1390 RPM, C89 = 50 Hz):
CW at 25.0 Hz = 25.0 x 1390/50 = 695 = 0x02B7
Example 2 (C87 = 1390 RPM, C89 = 50 Hz):
CCW at 44.5 Hz = - (44.5 x 1390/50) = - 1237 =
0xFB2B