EasyManua.ls Logo

LG ARWB80LA2 - Page 65

LG ARWB80LA2
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ENGLISH
Installation Manual 65
Example of manual valve addressing
(In case that an indoor unit of central control address "11" is connected to a valve #1 of an
HR unit)
Prerequisite for manual valve addressing: central control address of each indoor unit must be preset differ-
ently at its wired remote control
- Above setup must be done for all HR unit valves.
- The valve that is not connected with any indoor unit should be addressed with any other number than used
address numbers of the valves connected with indoor units.
(The valves does not work if the address numbers are same.)
Operation: None
Display: None
No.
1
2
3
4
5
Display and setup Setup and Contents
Operation: Turn dip S/W No.1 on to address valve #1
Display: Existing value saved in EEPROM is displayed in
7-SEG.
Operation: Set the digit of 10 to the number in Group High data
of the wired remote control connected to the corresponding
indoor unit to the valve #1 by pressing left tack S/W.
Display: Digit increasing with the times of pressing tack S/W is
displayed in left 7-SEG
Operation: Set the digit of 1 to the number in Group Low data
of the wired remote control connected to the corresponding
indoor unit to the valve #1 by pressing right tack S/W.
Display: Digit increasing with the times of pressing tack S/W is
displayed in right 7-SEG
Operation: Turn dip S/W No.1 off to save the address of
valve #1
Display: "11" displayed in 7-SEG disappears
SW01M SW03M SW04M
SW01M SW03M SW04M
SW01M SW03M
SW04M
SW01M SW03M
SW04M
SW01M SW03M SW04M

Related product manuals