28
ENGLISH
FUNCTIONAL SPECIFICATIONS AC Smart BACnet
Point
No.
Control/monitoring
Object Name
(XXX : Unit address)
Object
Type
Unit
Inactive Active
Text- 0 Text-1 Text-2 Text-3 Text- 4 Text-5
35
Occupancy (Setting)
OccupancyCommand_XXX
BO
Unoccupied Occupied
36
Occupancy (Status)
OccupancyStatus_XXX
BI
Unoccupied Occupied
37
2Set Cooling Set Temperature (Setting)
2SetCoolingTempCommand_XXX
AV °C
38
2Set Cooling Set Temperature (Status)
2SetCoolingTempStatus_XXX
AI °C
39
2Set Heating Set Temperature (Setting)
2SetHeatingTempCommand_XXX
AV °C
40
2Set Heating Set Temperature (Status)
2SetHeatingTempStatus_XXX
AI °C
41
2Set Cooling Upper Temperature
(Setting)
2SetCoolingUpperLimitCommand_
XXX
AV °C
42
2Set Cooling Upper Temperature (Status)
2SetCoolingUpperLimitStatus_XXX
AI °C
43
2Set Heating Upper Temperature
(Setting)
2SetHeatingUpperLimitCommand_
XXX
AV °C
44
2Set Heating Upper Temperature (Status)
2SetHeatingUpperLimitStatus_XXX
AI °C
45
2Set Cooling Lower Temperature
(Setting)
2SetCoolingLowerLimitCommand_
XXX
AV °C
46
2Set Cooling Lower Temperature (Status)
2SetCoolingLowerLimitStatus_XXX
AI °C
47
2Set Heating Lower Temperature
(Setting)
2SetHeatingLowerLimitCommand_
XXX
AV °C
48
2Set Heating Lower Temperature (Status)
2SetHeatingLowerLimitStatus_XXX
AI °C
49
Thermo Status (Status)
ThermoStatus_XXX
BI
Off On
35 ~ 49 points are effective, in case 2Set Auto Mode of environment setting is enabled.