49
ENGLISH
FUNCTIONAL SPECIFICATIONS AC Smart BACnet
Modbus Point List : Ventilation
Function Code : 0x01 and 0x05
Register Function Name
Object Name
(XXX : Ventilation address)
Inactive Active
1
Coil Read
ON/OFF StartStopStatus_XXX Stop Run
2 LOCK LockStatus_XXX Permit Prohibit
3 FI LTER SIG N FilterSign_XXX Off On
4 ALARM Alarm_XXX Stop Run
5 HRV_AC_OPER HrvStartStopStatus_XXX Stop Run
6 HRV_HUMIDIFY HrvHumidifyStatus_XXX Off On
1
Write Single
Coil
ON/OFF StartStopCommand_XXX Stop Run
2 LOCK LockCommand_XXX Permit Prohibit
3 FILTER SIGN RESET FilterSignReset_XXX Reset(Off) Void(On)
5 HRV_AC_OPER HrvStartStopCommand_XXX Stop Run
6 HRV_HUMIDIFY HrvHumidifyCommand_XXX Off On