Dedicated Outdoor Air System (DOAS) Installation and Operation Manual
START-UP
Error Codes
Error Code Error Error Cause
CH 01 Room Temperature Temperature sensor disconnection or short circuit
CH 02 Pipe In Temperature Sensor Error Temperature sensor disconnection or short circuit on pipe inlet of DOAS unit
CH 03
Communication Error Between Wired Remote Controller
and Communication Kit
No communication signal for more than 3 minutes from wired remote
controller to the communication kit
CH 05
Communication Error Between Communication Kit and
Outdoor Unit
No communication signal for 5 minutes continuously from communication kit
to outdoor unit
CH 06 Pipe Out Temperature Sensor Error Temperature sensor disconnection or short circuit on pipe outlet of DOAS unit
CH 09 Option PCB EEPROM Error No signal reading 5 continuous times from EEPROM to communication kit
Error Codes
Below is a list of possible error codes that will appear on an LG Programmable Thermostat if the DOAS is not communicating with the
outdoor unit.
Table 6: Error Codes
Once communication between outdoor units and DOAS unit is confirmed, you may proceed to the JENEsys AHU controller start up on next
page. Errors on the JENEsys controller are explained on page 38.