- 34 -
6. Wrap the insulation material around the connect-
ing portion.
Overlap the connection pipe insulation material
and the indoor unit pipe insulation material.
Bind them together with vinyl tape so that there
is no gap.
1. Route the indoor tubing and the drain hose to the
required piping hole position.
2. Insert the piping, drain hose and the connecting
cable into the piping hole.
When extending the drain hose at the indoor
unit, install the drain pipe.
Tighten the flare nut with a wrench.
18K, 24K, 26K
1/2"[5.5kg
.
m] 1/4"[1.8kg
.
m]
5/8"[6.6kg
.
m] 3/8"[4.2kg
.
m]
Pipe Size[Torque]
Capacity
(Btu/h)
GAS LIQUID
Wrap the area which accommodates the rear
piping housing section with vinyl tape.
Bundle the piping and drain hose together by
wrapping them with vinyl tape over the range
within which they fit into the rear piping housing
section.
For right rear piping