EasyManua.ls Logo

LG MULTI F - Page 54

LG MULTI F
361 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
54
MULTI F / MULTI F MAX Outdoor Unit Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
The LG-supplied Y-Branch kit PMBL5620 MUST be used when
installing two (2) branch distribution units in parallel on one (1) Multi
F MAX system.
Field-supplied fittings are not permitted. Each
Y-Branch kit includes two (2) Y-branches (one for the liquid line and
one for the vapor line) and insulation covers.
Y-branches can be installed in horizontal or vertical configurations.
When installed vertically, position the Y-branch so the straight
WKURXJKOHJLVRISOXPE:KHQLQVWDOOHGKRUL]RQWDOO\SRVLWLRQWKH
Y-branch so the take-off leg is level and shares the same horizontal
SODQHDVWKHVWUDLJKWWKURXJKOHJURWDWLRQ
Y-branches must be properly installed following instructions in the
applicable LG manual. Y-branches must always be installed with the
single port facing the outdoor unit and the two-port end facing the
branch distribution units.
Do not install Y-branches backwards
as refrigerant flow cannot make U-turns. The Y-branch kit must be
located at least three (3) feet from the outdoor unit. Provide a min-
imum of 20 inches between a Y-branch and the branch distribution
unit.
When a Y-branch is located in a pipe chase or other concealed
space, access doors must be provided for inspection access.
7KHHTXLYDOHQWSLSHOHQJWKRIHDFK<EUDQFKƍPXVWEHDGGHGWR
the main pipe segment entered into LATS piping design software.
Figure 54: <%UDQFK3RUW,GHQWL¿HU'LDJUDP
Figure 55: Y-Branch Dimensions Diagram.
Figure 56: +RUL]RQWDO&RQ¿JXUDWLRQ(QG9LHZ
Figure 57: <EUDQFK,QVWDOODWLRQ$OLJQPHQW6SHFL¿FDWLRQ
Viewed from A in direction of arrow
Horizontal
plane
Within 5°
A
Within 5°
Vertical Up
Configuration
Within ± 3°Within ± 3°
Vertical Down
Configuration
A
B
X
Y
1
2
3
A = To Outdoor Unit B = To Branch Distribution Unit
1
2
3
Multi F MAX Y-Branch Kit PMBL5620
Design pressure is 551 psig.
All dimensions in inches. Tolerance ±1/4 inch.
Images are not to scale.
Table 30: Y-Branch Connection Diameters.
INSTALLING MULTI F MAX SYSTEMS
Model
Y-Branch
Type
3RUW,GHQWLÀHULQFK Dimensions
123XY
PMBL5620
Liquid 3/8 3/8 3/8 13.80 3.24
Vapor 3/4 3/4 3/4 12.48 3.02

Table of Contents

Other manuals for LG MULTI F

Related product manuals