60
MULTI V Ceiling Cassette Indoor Units
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
7ZR:D\76)UDPH
WIRING
Table 17: TS Frame Wiring Diagram Legend.
Table 18: TS Frame DIP Switch Settings.
DIP Switch Setting Off On Remarks
SW3 GROUP CONTROL Master Slave
Group control setting using 7-Day Programmable Controller; selects
Master/ Slave on each indoor unit
SW4
DRY CONTACT
MODE
Variable Auto
Sets operation mode for optional Dry Contact accessory
1. Variable: Auto or Manual Mode can be set through 7-Day
Programmable Controller or Wireless Remote Controller
(factory default setting is Auto if there is no setting)
2. Auto: For Dry Contact, it is always Auto mode
*For Gen 4 Multi V two-way ceiling cassette indoor units, DIP switches 1, 2, 5 through 8 must be set to OFF. These DIP
switches are used for other models.
**To enable Generation 4 features, outdoor unit DIP switch no. 3 must be set to ON. Please refer to the Multi V 5, Multi V IV,
Multi V Water IV, Multi V S Engineering Manual for additional information.
Terminal Purpose Function
CN-MOTOR1 Fan motor output Motor output of BLDC
CN-EEV EEV Output EEV Control output
CN-CC Dry Contact Dry Contact
CN-OPTION Option PCB (EEPROM) Option PCB connection
CN-ROOM Room sensor Room air thermistor
CN-PIPE_IN Suction pipe sensor Pipe in thermistor
CN-HUMID N/A N/A
CN-PIPE_OUT Discharge pipe sensor Pipe out thermistor
CN-LEAK Leak sensor Leak sensor connection
CN_EXT External on/off controller External on/off controller connection
CN-FLOAT Float switch input Float switch sensing
CN_WF Wi-Fi module Wi-Fi module connection
CN_DCDRAIN Drain pump output AC output for drain pump
CN-AIRC N/A N/A
CN-PTC Auxiliary heater Auxiliary heater connection
CN-DISPLAY Display Display of indoor status
CN-VANE1 Step Motor Step motor output
CN-485 Communication Connection between indoor and outdoor units
CN-COM Communication Connection on Sub PCB between indoor and outdoor units
CN-REMO Remote controller Remote control line
CN-POWER AC Power supply AC Power line input for indoor controller
*If a Third-Party Dry Contact and an LG internal heater or an LG Auxiliary Heater Kit is installed, supplemental heat capability cannot be controlled by the Third-Party Thermostat.