63
Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
)RXU:D\7574)UDPHV
WIRING
Table 19: TR / TQ Frame Wiring Diagram Legend.
Table 20: TR / TQ Frame DIP Switch Settings.
*For Gen 4 Multi V four-way ceiling cassette indoor units, DIP switches 1, 2, 5, 6, and 8 must be set to OFF. These DIP switch-
es are used for other models.
**To enable Generation 4 features, outdoor unit DIP switch no. 3 must be set to ON. Please refer to the Multi V 5, Multi V IV,
Multi V Water IV, Multi V S Engineering Manual for additional information.
DIP Switch Setting Off On Remarks
SW3 GROUP CONTROL Master Slave
Group control setting using 7-Day Programmable Controller; selects Master /
Slave on each indoor unit
SW4
DRY CONTACT
MODE
Variable Auto
Sets operation mode for optional Dry Contact accessory
1. Variable: Auto or Manual Mode can be set through 7-Day
Programmable Controller or Wireless Remote Controller
(factory default setting is Auto if there is no setting)
2. Auto: For Dry Contact, it is always Auto mode
SW7
VENTILATOR
INTERLOCK
Off On
Selects ventilator interlock function for four-way ceiling cassette indoor units.
1. On: Automatic (vent relay will be turned on after ten [10] seconds
of indoor unit operation
2. Off: Manual (ventilator needs to be set through the controller)
Terminal Purpose Function
CN_MOTOR1 Fan motor output Motor output of BLDC
CN_WF Wi-Fi module Wi-Fi module connection
CN-PTC Auxiliary heater Auxiliary heater connection
CN_DUST N/A N/A
CN_FLOAT Float switch input Float switch sensing
CN_EEV EEV output EEV control output
CN_DISPLAY Display Display of indoor status
CN_OPTION Option PCB (EEPROM) Option PCB connection
CN_ROOM Room sensor Room air thermistor
CN_PIPE_IN Suction pipe sensor Pipe in thermistor
CN_HUMID N/A N/A
CN_LEAK Leak sensor Leak sensor connection
CN_PIPE_OUT Discharge pipe sensor Pipe out thermistor
CN_EXT External on/off controller External on/off controller connection
CN_CC Dry Contact Connection to Dry Contact (Optional)
CN_AIRC* Air cleaner Air cleaner control
CN_VANE2 Step Motor Step motor output
CN_VANE1 Step Motor Step motor output
CN_DCDRAIN Drain pump output AC output for drain pump
CN_485 Communication Connection between indoor and outdoor units
CN_COMM Communication Connection on Sub PCB between indoor and outdoor units
CN_REMO Remote controller Remote control connection
CN_POWER AC Power supply AC power line input for indoor controller
*If a Third-Party Dry Contact and an LG internal heater or an LG Auxiliary Heater Kit is installed, supplemental heat capability cannot be controlled by the Third-Party Thermostat.