5. Wiring Diagrams
 
CONNECTOR NUMBER
                             SPEC.                                                        DESCRIPTION
   CN-MOTOR1                     Fan motor output                                  Motor output of BLDC
   CN-MOTOR2                     Fan motor output                                  Motor output of BLDC
   CN-PIPE_OUT                  Discharge pipe sensor                         Pipe out thermistor
   CN-PIPE_IN                      Suction pipe sensor                             Pipe in thermistor
   CN-ROOM                         Room sensor                                        Room thermistor
   CN-REMO                         Remote controller                                 Remote control line
   CN-FLOAT                        Float switch input                                 Float switch sensing
   CN-EEV                             EEV output                                           EEV control output
   CN-D_PUMP                     Drain pump output                               AC output for drain pump
   CN-OPTION                      Option PWB.                                        Communication between main and option
   CN-COM                            Communication                                    Communication between indoor and outdoor
   CN-POWER                      AC power supply                                  AC power line input for indoor controller
   CN-ZONE                          Zone Controller                                    Zone control line 
   CN-DISPLAY                     RF Remote controller                           RF remote control line 
   CN-CC                               Dry contact                                           Dry contact line 
   CN-EXT                           External On/Off                                 External On/Off signal input
L2/L3 Chassis
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
Function Description Setting Off Setting On
Default
SW1
Communication
N/A (Default) - - Off
SW2
Cycle
N/A (Default) - - Off
SW3
Group Control
Selection of Master or Slave
Master Slave Off
SW4
Dry Contact Mode
Selection of Dry Contact Mode
Wired/Wireless remote controller selec-
tion of Manual or Auto operation Mode
Auto Off
SW5
Installation
Fan continuous operation
Continuous operation Removal - Off
SW6
Heater linkage
N/A - - Off
SW7
Ventilator linkage
Selection of Ventilator linkage
Linkage Removal Working
Off
Vane selection (Console)
Selection of up/down side Vane
Up side + Down side Vane
Up side Vane Only
Region selection
Selection tropical region General model Tropical model
SW8
Etc.
Spare - - Off