2 _ Fresh Air Intake Unit
Indoor Units
Notes:
1. Capacities are based on the following conditions:
      Cooling      • Outdoor temp. 33°C[91.4°F]DB/ 28°C[82.4°F]WB
                        • Interconnecting Piping Length 7.5m
                       • Level Difference of Zero
      Heating      • Outdoor temp. 0°C[32°F]DB/ -2.9°C[26.78°F]WB
                        • Interconnecting Piping Length 7.5m
                        • Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. Indoor Unit Connection
6. EEV : Electronic Expansion Valve
7. Noise Level is Standard Mode
(for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dBA)
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
3
/min x 35.3
l/s = CMM x 1000/60 
 Type
 Model                                Unit
                                                                        kW
 Cooling Capacity                                         kcal/h
                                                                      Btu/h
                                                                        kW
 Heating Capacity                                         kcal/h
                                                                      Btu/h
 Casing  
 
Dimensions(WxHxD)
 
Body
                                  mm
                                                                       inch
 
Coil
 
Rows x Columns x FPI
 
                             Face Area                           m
2
                             Type 
 
Motor Output x Number  
W
                             Running Current                  A
 
Fan
                     Air Flow Rate(H/M/L)        CMM
 
(High Mode-factory set)
         cfm
 
External Static Pressure
  mmAq(Pa)
                             Drive  
                             Motor type 
 Temperature Control  
 Sound Absorbing Thermal Insulation Material 
 Air Filter
 Safety Device  
 
 
Liquid Side                    mm(inch)
 
Pipe Connections
  Gas Side                       mm(inch)
 
Drain Pipe(Internal Dia.)
          mm
 Net Weight                                                  kg(lbs)
 Noise Level
(Sound Press, 1.5m, H/M/L)
       dB(A)
 Power Supply                                            Ø, V, Hz
 Refrigerant Control  
 Power cable                                                  mm
2
 Transmission cable                                       mm
2
 ARNU48GBRZ4                ARNU76GB8Z4                ARNU96GB8Z4
                 14.1                                   22.4                                    28
               12,100                               19,300                               24,100
               48,100                               76,400                               95,900
                 13.5                                   21.4                                   26.7
               11,620                               18,410                               23,000
               46,115                               73,080                               91,360
  Galvanized Steel Plate      Galvanized Steel Plate     Galvanized Steel Plate
      1,230 x 380 x 590              1,562 x 460 x 688             1,562 x 460 x 688 
 48-7/16 x 14-31/32 x 23-7/32      61-1/2 x 18-1/8 x 27-3/32         61-1/2 x 18-1/8 x 27-3/32 
           3 x 13 x 19                         3 x 20 x 19                        3 x 20 x 19
                 0.38                                   0.59                                   0.59
           Sirocco Fan                       Sirocco Fan                      Sirocco Fan
              195 x 1                              375 x 1                              375 x 1
                 0.78                                   1.36                                   2.15
         18.8/14.7/14.7                   23.7/13.2/13.2                   35.7/23.7/23.7
          664/519/519                      837/446/446                     1261/837/837
                  18                                      22                                      22
               Direct                                 Direct                                Direct
               BLDC                                 BLDC                                BLDC
       Microprocessor,                 Microprocessor,                Microprocessor, 
  Thermostat for cooling      Thermostat for cooling      Thermostat for cooling 
           and heating                       and heating                       and heating
     Foamed polystrene           Foamed polystrene           Foamed polystrene
        Long Life Filter                  Long Life Filter                  Long Life Filter
                Fuse                                  Fuse                                  Fuse
            Ø9.52(3/8)                         Ø9.52(3/8)                        Ø9.52(3/8)
           Ø15.88(5/8)                       Ø19.05(3/4)                       Ø22.2(7/8)
                  25                                      25                                      25
               45(99)                               73(161)                             73(161)
             41/40/38                            45/43/43                            47/45/45
        1, 220 - 240, 50                 1, 220 - 240, 50                1, 220 - 240, 50
            1, 220, 60                          1, 220, 60                          1, 220, 60
                 EEV                                   EEV                                  EEV
           CV1.5 x 3C                        CV1.5 x 3C                       CV1.5 x 3C
  VCTF-SB1.0 ~ 1.5 x 2C   VCTF-SB 1.0 ~ 1.5 x 2C  VCTF-SB 1.0 ~ 1.5 x 2C
Fresh Air Intake Unit
  No                         Connection Condition                                                                                                          Combination
Fresh Air Intake Units only are connected with
outdoor units
Mixture connection with general Indoor unit and
Fresh Intake Unit
  1
                                                                                        1) The total capacity of Fresh Air Intake Unit should be 50~100% of outdoor unit.
2) The max quantity of Fresh Air Intake unit is 4 Units.
  2
                                                                                        1) The total capacity of indoor units (standard Indoor Unit + Fresh Air Intake Unit) should be 50~100% of out-
door unit.
                                                                                            2) The total capacity of Fresh Air Intake Unit should be less than 30% of the total capacity of indoor units.
2. Specifications