PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
29
ENGLISH
Y branch method
1 Outdoor Units
Example : 5 Indoor Units connected
: Outdoor Unit
: 1st branch (Y branch)
: Indoor Units
2 Outdoor Units
Example : 5 Indoor Units connected
: Outdoor Unit
: 1st branch (Y branch)
: Indoor Units
: Downward Indoor Unit
: Connection branch pipe between Outdoor
units: ARCNN21
l 40m (90 m : Conditional application)
h 40m
H 110m
L150m (200 m : Conditional application)
Master
Master
Slave
Slave
Master
Slave
l 40m (90 m : Conditional application)
H 110m
L150m (200 m : Conditional application)
h 40m
10m or
less
h1
ODU Capacity
Master ≥ Slave
Piping length from outdoor branch to outdoor unit 10m, equivalent length:max 13m
(for 22HP or more)
Conditional Application
To satisfy below condition to make 40 m ~ 90 m of pipe length after first branch.
• Diameter of pipes between first branch and the last branch should be increased by one
step, except pipe diameter B,C,D is same as Diameter A
Ø6.35
Ø 9.52
Ø 12.7
Ø 15.88
Ø 19.05
Ø 22.2
Ø 25.4*, Ø 28.58
Ø 31.8*,
Ø 34.9
Ø 38.1*
* : It is not necessary to size up.
• While calculating whole refrigerant pipe length, pipe B,C,D length should be calculated
twice.
A+Bx2+Cx2+Dx2+a+b+c+d+e 1,000 m
• Length of pipe from each indoor unit to the closest branch (a,b,c,d,e) 40 m
• [Length of pipe from outdoor unit to the farthest indoor unit 5 (A+B+C+D+e)]
- [Length of pipe outdoor unit to the closest indoor unit 1 (A+a)] 40 m