EasyManuals Logo

LG MULTI V IV ARNU12GTU 2 Series User Manual

LG MULTI V IV ARNU12GTU 2 Series
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #110 background imageLoading...
Page #110 background image
Troubleshooting Guide
- 110 -
Copyright ©2013 LG Electronics. Inc. All right reserved.
Only for training and service purposes
LGE Internal Use Only
1. Power cable or communication cable is not
connected
2. Defect of outdoor Main PCB or
Comp1/Comp2 PCB
Error
No.
Error Type Error Point Main Reasons
Main PCB of Master unit
of Master unit canʼt
receive signal from
Comp1/Comp2 controller
Communication error
between
(Comp1/Comp2 PCB
Main PCB)
52*
Master 521
Slave1 522
Slave2 523
Slave3 524
n Error diagnosis and countermeasure flow chart
Is communication
LED (Yellow) of
Comp1/Comp2 PCB
PCB on?
No
Re-connect communication cable
Is communication cable
connected correctly?
Yes
No
Re-connect communication cable
Is Main PCB normal?
Yes
No
Replace Main PCB
Replace Comp1/Comp2 PCB
* The method of checking Main PCB and Comp1/Comp2 PCB (If normal, communication LED blinks)
Yes
Communication Connector &
LED in Comp1 PCB
Communication Connector &
LED in Comp2 PCB
Comp1 Communication
Connector
Comp1 Communication
LED
Com2 Communication
LED
Comp2 Communication
Connector

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG MULTI V IV ARNU12GTU 2 Series and is the answer not in the manual?

LG MULTI V IV ARNU12GTU 2 Series Specifications

General IconGeneral
BrandLG
ModelMULTI V IV ARNU12GTU 2 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals