4.6 ITR(Cooling)
This function is checking process for normal operation of parts and system On operating system.
• Saved data can check using LGMV.
Start
All IDU operation on
Fan mode on 1 minute
Check Temp. Condition
Yes
No
System off
Stop operation and judge
the result
Judge IDU EEV
Switchover 4way valve
All IDU operation(refrigerant
check) and save data
(All-1) IDU operation and
save data
1 IDU operation and
save data
Judgment Code Display
ITR(Cooling)
IDU EEV
OK 5-Cn
NG 5-C1
Impossible to Judge 5-CF
Refrigerant
More than standard ex) 20%
Less than standard ex) -15%
Don't Adjustment required 00
Impossible to Judge 3-CF
Function