2.1 Oil return control
2.1.1 Oil return control on cooling mode
Oil return operation recovers Oil level in compressor by collecting oil accumulated in pipe.
Each cycle component operates as shown on the below table during oil return operation.
n Oil return operation time : 3 min for running step
n Starting condition : When low oil level which is measured by oil level sensor is kept continuously then oil
return operation will be start.
n Oil return process ends if compressor protection control starts
Min. pulse
Upper : Min. pulse
Low : Max. pulse
Upper : Min. pulse
Low : Max. pulse