EasyManuals Logo

LG MULTI V M ARNU07GTU 4 Series User Manual

LG MULTI V M ARNU07GTU 4 Series
91 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
- 16 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
1.3 EEV control
(1) Main EEV control
Main EEV operates with fuzzy control rules to keep the degree of super Heat(Superheat) (about 3°C)at
the evaporator outlet stable during heating mode
The degree of Superheat = Tsuction - Tevaporation
Tsuction : temperature at suction pipe sensor(°C)
Tevaporation : evaporation temperature equivalent to low pressure(°C)
(2) Subcooling EEV control(about 15°C)
Subcooling EEV works with fuzzy rules to keep the degree of Subcool at the outlet of subcooler during
cooling mode
The degree of Subcool = Tcondensation - Tliquid
Tliquid : temperature at outlet of subcooler(°C)
Tcondensation : condensation temperature equivalent to high pressure(°C)
(3) Avoiding excessive high discharge temperature : when main EEV opens some given opening and dis-
charge temperature is above 85°C in heating operation, subcooling EEV may control the "subcooling
out temperature-evaporating temperature" to be some given difference.
Function

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG MULTI V M ARNU07GTU 4 Series and is the answer not in the manual?

LG MULTI V M ARNU07GTU 4 Series Specifications

General IconGeneral
BrandLG
ModelMULTI V M ARNU07GTU 4 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals