48
ENGLISH
Switch (Up)
Switch (Down)
Left side
Right side
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• If use a function, first install a Cool & Heat selector.
Setting the outdoor unit address (Fn 5)
How to set the mode
Turn on DIP switch No.5 of the master unit PCB
Use ‘‘ and ‘‘ button to mark “Func” in the 7
segment, and press ‘‘ button.
Use ‘‘ and ‘‘ button to mark “Fn5” in the 7
segment, and press ‘‘ button.
Use ‘‘ and ‘‘ button to select one among “0” ~
“254” in the 7 segment, and press ‘‘ button.
Outdoor unit address is set.
CAUTION
!
• Request the function settings to the installation specialist during
the outdoor unit installation.
• If use a function, first install a Central controller.
Target pressure adjusting (Fn 8)
How to set the mode
Turn on DIP switch No.5 of the master unit PCB
Use ‘‘ and ‘‘ button to mark “Func” in the 7
segment, and press ‘‘ button.
Use ‘‘ and ‘‘ button to mark “Fn8” in the 7
segment, and press ‘‘ button.
Select the Option using ‘’, ‘’ Button :
“op1” ~ “op4” Push the ‘’ button
Decide target pressure according to the set mode.
Select the Option using ‘’, ‘’ Button :
“HEAT”, “COOL” Push the ‘’ button
CAUTION
!
• Ask an authorized technician to setting a function.
• If do not use a function, set an off-mode.
• Change a power consumption or capacity.
Setting
mode
Purpose
Condensing
temperature
variation
Evaporating
temperature
variation
“Heat” “Cool”
op1
Increase
capacity
Increase
capacity
-3 °C (26.6 °F) +2 °C (35.6 °F)
op2
Decrease power
consumption
Increase
capacity
-1.5 °C (29.3 °F) -2 °C (28.4 °F)
op3
Decrease power
consumption
Decrease power
consumption
+2.5 °C (36.5 °F) -4 °C (24.8 °F)
op4
Decrease power
consumption
Decrease power
consumption
+4.5 °C (40.1 °F) -6 °C (21.2 °F)
Master unit PCB DIP switch on : No.5
Select the mode using ‘’, ‘’ Button : “Func” Push
the ‘’ button
Select the Function using ‘’, ‘’ Button : “Fn 12”
Push the ‘’ button
Select the Option using ‘’, ‘’ Button :
“oFF”,“op1”,“op9” Push the ‘’ button
Cool & Heat Selection mode is set
Compressor Max. Frequency Limit (Fn 12)
Mode setting method
Mode setting
- ON: Set to control the Low capacity mode
- OFF: Set not to control
Turn on DIP switch No.5 of the master unit PCB
Use ‘‘ and ‘‘ button to mark “Func” in the 7
segment, and press ‘‘ button.
Use ‘‘ and ‘‘ button to mark “Fn7” in the 7
segment, and press ‘‘ button.
Use ‘‘ and ‘‘ button to select between “ON” and
“OFF” in the 7 segment, and press ‘‘ button.
IDU capacity adjusting mode is set
IDU capacity adjusting (Fn 7)
If the operation of indoor unit is more than 130 %, the air flow is
operated as low in the all indoor units.
How to set the mode
CAUTION
!
• Ask an authorized technician to setting a function.