Cooling change of temperature - Air Conditioners
Room Air Room Air LP070CE* LP090CE* LP120CE* LP150CE*
Dry Wet Temperature Across Temperature Across Temperature Across T
emperature Across
Bulb Bulb Indoor Coil (∆ T) Indoor Coil (∆ T) Indoor Coil (∆ T)
Indoor Coil (∆ T)
Min Max Min Max Min Max Min Max
Rating Btu/h 7000 7600 9000 9300 11700 12000 14300
14600
Rating CFM 185 225 230 260 300 330 315 355
85 1 3 2 6 1 5 1 4
80 8 13 11 14 9 13 8 12
90 75 19 22 19 22 18 22 16 20
70 30 33 28 30 26 30 25 27
80 4 9 7 11 5 10 5 8
75 14 19 15 18 13 18 12 16
85 70 23 27 23 25 21 25 20 23
65 34 36 31 33 29 33 28 30
75 9 14 11 14 9 13 8 12
70 18 21 18 20 15 20 15 18
80 65 26 29 24 27 23 26 21 24
60 35 36 32 33 29 33 29 30
70 12 16 13 16 10 15 10 14
65 18 22 18 21 15 20 15 19
75 60 25 28 23 26 21 25 20 24
55 31 34 28 31 26 30 26 28
65 12 15 12 14 9 13 9 13
70 60 17 20 16 18 13 17 13
17
55 22 24 20 22 18 21 17
21
Model
Room Air Room Air LP070HE* LP090HE* LP120HE* LP150HE*
Dry Wet Temperature Across Temperature Across Temperature Across T
emperature Across
Bulb Bulb Indoor Coil ( ∆ T) Indoor Coil ( ∆ T) Indoor Coil ( ∆ T) Indoor Coil ( ∆
T)
Min Max Min Max Min Max Min Max
Rating Btu/h 7300 7600 9300 9600 12300 12600 14300
14600
Rating CFM 195 225 240 270 310 340 315 355
85 13 26 151 4
80 8 13 11 15 10 13 8 12
90 75 19 22 19 22 18 22 17 20
70 30 33 29 30 26 30 25 28
80 4 9 7 11 5 10 5 9
75 14 19 15 18 14 18 12 16
85 70 23 27 23 25 21 25 21 23
65 33 36 31 33 30 33 28 31
75 9 14 11 15 10 13 8 12
70 18 21 18 20 16 20 16 18
80 65 26 29 24 27 23 26 22 25
60 35 36 32 33 30 33 29 31
70 12 16 13 16 11 15 10 14
65 18 22 18 21 16 20 16 19
75 60 24 28 23 26 21 25 21 24
55 31 34 29 31 26 30 26 29
65 12 15 12 15 10 13 9 13
70 60 17 20 16 18 14 17 13
17
55 22 24 20 22 18 21 18
21
Cooling Change of Temperature - Heat Pumps