AHU CONTROL KIT SETTINGS
ENGLISH
EEV Module
(EEV Module)
Capacity Settings
Use DIP switch SW1 to set the capacity.
* When connecting a high-capacity EEV kit (PRLK396A0, PRLK594A0), set the capacity to
56.4 kW.
Address Setting
DIP switch SW2 is the address setting function. When the product is shipped from the factory,
the addresses are set as follows.
EEV #1,2,3 are included and EEV #4,5,6 are optional.(After purchasing separately, additional
setting required.)
SW1
1234Capacity [kW (kBtu/h)]
OFF OFF OFF OFF 2.1 (7)
OFF OFF OFF ON 2.5 (9)
OFF OFF ON OFF 3.5 (12)
OFF OFF ON ON 5.6 (18)
OFF ON OFF OFF 7.1 (24)
OFF ON OFF ON 8.2 (28)
OFF ON ON OFF 10.6 (36)
OFF ON ON ON 12.3 (42)
ON OFF OFF OFF 14.1 (48)
ON OFF OFF ON 22.4 (76)
ON OFF ON OFF 28.0 (96)
ON OFF ON ON 33.6 (115)
ON ON OFF OFF 39.2 (134)
ON ON OFF ON 44.8 (153)
ON ON ON OFF 50.5 (172)
ON ON ON ON 56.4 (192)
Sequence
SW2
Address Remark
1 2 3 4
EEV #1 OFF OFF OFF
OFF
Internal address 0
EEV #1,2,3
Included
EEV #2 OFF OFF ON Internal address 1
EEV #3 OFF ON OFF Internal address 2
EEV #4 OFF ON ON Internal address 3
EEV #4,5,6 Optional :
Additional setting required
EEV #5 ON OFF OFF Internal address 4
EEV #6 ON OFF ON Internal address 5