INSTALLATION METHOD
ENGLISH
INSTALLATION METHOD
Diagram of overall product configuration
When interlocked to pulse type wattmeter
• When interlocked to EHP product
- Independent Operation of Power Indicator (interlocked to EHP products)
Power cable for 3 phase 4 wire
Power cable for single phase
Communication cable (2 wire shielded cable): Between outdoor unit and central controller
Communication cable (2 wire shielded cable): Between indoor unit and outdoor unit
Pulse signal wire
Refrigerant pipe
CAUTION
• Depending on the electric power, use the wattmeter for remote reading by sending the
pulse signal.
• Use the wattmeter with the pulse width of 50 - 400msec.
• The wattmeter pulse must be able to sink at least 3mA or more of current in the power
indicator.
• Use the wattmeter of 1W/pulse, 2W/pulse, 4W/pulse, 6W/pulse, 8W/pulse, 10W/pulse,
100W/pulse and PT/CT (1-50,000).
• When setting the wattmeter, set it to Master Mode.
• Maximum of 8 wattmeters can be installed.
• The distance between power indicator and wattmeter should be shorter than 10m in
normal circumstance.
• When electrical or mechanical noise is expected, more shorter wiring is needed.
h EHP (Electric Heat Pump): It is an electric air conditioner to drive the compressor by electric power.
!