EasyManua.ls Logo

LG TMNC092DYAA - Operation Details

LG TMNC092DYAA
51 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Multi Air Conditioner
Operation Details
Operation Details
Function of Controls
• DISPLAY
C/O Model
Operation Indicator
ON while in appliance operation, OFF while in appliance pause.
Sleep Mode
Comp. Running Incidator
Cooling Mode Operation
When the intake air temperature reaches0.5 °C below the setting temp, the compressorand the outdoor fan
stop.
When itreaches0.5 °C above the setting temp, they start to operate again.
Compressor ON Temp
Setting Temp+0.5°C
Compressor OFF Temp
Setting Temp-0.5°C
While in compressorrunning, operating with the
speedset by the remote control. While in compressor
Health
•Whenthe operation input by the remote control is received,the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C Intake Air Temp
25°C
24°C Intake Air Temp<26°C
Intake Air Temp-1°C
18°C Intake Air Temp<24°C
Intake Air Temp-0.5°C
Intake Air Temp<18°C
18°C
Whilethe intake air temp is between compressoron temp. and compressor temp.,10-min
Compressor ON Temp. Setting Temp+0.5°C
Compressor OFF Temp.
Setting Temp-0.5°C
Energy Saving Mode
2