9
MULTI/SINGLE CAC
Installation of Outdoor Units
4. Refrigerant piping system
4.1 Piping System between outdoor unit / indoor unit
Single type
CAUTION
• Please check the product type. Piping installation and refrigerant charge varies depending on the type of
product.
For more information, please refer to the installation manual.
Refrigerant additional charge calculation method
Additional Refrigerant = (L - A) x a
L (m) : Installed Piping Length (Outdoor Unit ~ Indoor Unit)
A (m) : Charge-less piping length
a (g/m) : Additional charging volume
* Refer to the specifications for detail information of A, a.
* If total additional charge value after calculation comes out to be negative, then do not consider additional charge.
CAUTION
• Capacity is based on standard length and maximum allowance length is on the basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
Indoor Unit
Indoor Unit
L
H
L
H
Notes
L (m) : Piping Length (Outdoor Unit ~ Indoor Unit)
H (m) : Height Difference (Outdoor Unit ~ Indoor Unit)
Refer to the specifications of Outdoor Unit for Maximum limit.