11
MULTI/SINGLE CAC
Installation of Outdoor Units
5. Installation guide at the seaside
CAUTION
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas,
are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result
corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause
product malfunctionor inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind.
Otherwise itneeds additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
1. If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.
2. In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
3. Select a well-drained place.
Note
Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
It should be strong enough like concrete to prevent
the sea wind from the sea.
The height and width should be more than 150% of
the outdoor unit.
It should be kept more than 70 cm of space between
outdoor unit and the windbreak for easy air flow.
Sea wind
Sea wind
Sea wind
Windbreak