EasyManuals Logo

Liebert HPSE User Manual

Liebert HPSE
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
7
Technical Data
7--1
Liebert HPS---PD--- 272965---20.11.2009
Ta b . 1 --- HPSE + HPSC (No freecooling version)
MODEL: H PS 06 08
Air supply --- Downflow
Main power supply --- 230V±10%/1Ph/50Hz 400V±10%/3Ph+N+PE/50Hz
PERFORMANCE
Total cooling capacity
(1)
Sensible cooling capacity
(1)
Compressor --- AC power input
(1)
Compressor --- AC operative current (OA)
(1)
Compressor --- AC max current (FLA)
Compressor --- AC starting current (LRA)
Condenser fan --- AC power input
(1)
Condenser fan --- AC max. power input
Condenser fan --- AC operative current (OA)
(1)
Condenser fan --- AC max. current (FLA)
C o n d e n s e r f a n --- A C s t a r t --- u p c u r r e n t
Evaporator fan --- AC power input
(1)
Evaporator fan --- AC operative current (OA)
(1)
Evaporator fan --- AC max. current (FLA)
(2)
Evaporator fan --- AC start---up current
Evaporator air flow
Condenser max. air flow
Outdoor Sound Pressure Level
(3)
Indoor Sound Pressure Level
(3)
Max. ambient temperature
(4)
kW
kW
kW
A
A
A
kW
kW
A
A
A
kW
A
A
A
m
3
/h
m
3
/h
dB(A)
dB(A)
_C
6.4
6.4
1.58
7.6
11.4
47.0
0.08
0.08
0.6
1.4
1.6
0.18
0.8
1.0
1.3
1510
2170
50
58
47
8.2
8.2
2.18
3.9
5.1
32.0
0.10
0.10
0.7
1.4
1.6
0.35
1.5
2.0
2.7
2440
1920
50
62.5
45
REFRIGERATION CIRCUITS
Compressor --- type / quantity
Refrigerant
Expansion device
Evaporator coil --- tubes / fins material
Condenser coil --- tubes / fins material
---
---
---
---
---
Scroll / 1
R407C
Capillary
Copper / Aluminium
Copper / Aluminium
AIR FILTRATION
Main air filter --- quantity / type
Efficiency (CEN --- EU)
---
---
3/Panelfilters
G3
Filters dimensiond (DX side) mm 597 / 267 / 10
EVAPORATOR FAN
Quantity / Type / Poles --- 1 / Axial / 4
Driven / Motor protection --- Direct / IP44 Direct / IP54
CONDENSER FAN
Quantity / Type / Poles --- 1 / Axial / 6
Driven / Motor protection --- Direct / IP54
Control system --- Single speed
ELECTRIC HEATING
Type / Steps --- Wires / 1
Heating capacity kW 1.5 3.0
H e a t i n g --- m a x . c u r r e n t A 6 . 5
CABINET
Frame --- Galvanised steel
Painting --- Polyester --- RAL7035
OVERALL DIMENSIONS
Width / Height / Depth (HPSC outdoor unit) mm 920 / 840 / 390
Width / Height / Depth (HPSE indoor unit) mm 800 / 310 / 800
Weight (HPSC outdoor unit) kg 80 82
Weight (HPSE indoor unit) kg 50 53
Notes:
(1) Indoor reference conditions: 30˚C / 35% R.H. air intake. Outdoor reference conditions: 35˚C. Nominal power supply.
(2) Values referred to nominal speed (factory set).
(3) --- Measured with max. outdoor temperature at 2 m from the unit, in free field conditions.
(4) --- Maximum outdoor temperature referred to 30˚C / 35% R.H. air intake.