7
Technical Data
7--1
Liebert HPS---PD--- 272965---20.11.2009
Ta b . 1 --- HPSE + HPSC (No freecooling version)
MODEL: H PS 06 08
Air supply --- Downflow
Main power supply --- 230V±10%/1Ph/50Hz 400V±10%/3Ph+N+PE/50Hz
PERFORMANCE
Total cooling capacity
(1)
Sensible cooling capacity
(1)
Compressor --- AC power input
(1)
Compressor --- AC operative current (OA)
(1)
Compressor --- AC max current (FLA)
Compressor --- AC starting current (LRA)
Condenser fan --- AC power input
(1)
Condenser fan --- AC max. power input
Condenser fan --- AC operative current (OA)
(1)
Condenser fan --- AC max. current (FLA)
C o n d e n s e r f a n --- A C s t a r t --- u p c u r r e n t
Evaporator fan --- AC power input
(1)
Evaporator fan --- AC operative current (OA)
(1)
Evaporator fan --- AC max. current (FLA)
(2)
Evaporator fan --- AC start---up current
Evaporator air flow
Condenser max. air flow
Outdoor Sound Pressure Level
(3)
Indoor Sound Pressure Level
(3)
Max. ambient temperature
(4)
kW
kW
kW
A
A
A
kW
kW
A
A
A
kW
A
A
A
m
3
/h
m
3
/h
dB(A)
dB(A)
_C
6.4
6.4
1.58
7.6
11.4
47.0
0.08
0.08
0.6
1.4
1.6
0.18
0.8
1.0
1.3
1510
2170
50
58
47
8.2
8.2
2.18
3.9
5.1
32.0
0.10
0.10
0.7
1.4
1.6
0.35
1.5
2.0
2.7
2440
1920
50
62.5
45
REFRIGERATION CIRCUITS
Compressor --- type / quantity
Refrigerant
Expansion device
Evaporator coil --- tubes / fins material
Condenser coil --- tubes / fins material
---
---
---
---
---
Scroll / 1
R407C
Capillary
Copper / Aluminium
Copper / Aluminium
AIR FILTRATION
Main air filter --- quantity / type
Efficiency (CEN --- EU)
---
---
3/Panelfilters
G3
Filters dimensiond (DX side) mm 597 / 267 / 10
EVAPORATOR FAN
Quantity / Type / Poles --- 1 / Axial / 4
Driven / Motor protection --- Direct / IP44 Direct / IP54
CONDENSER FAN
Quantity / Type / Poles --- 1 / Axial / 6
Driven / Motor protection --- Direct / IP54
Control system --- Single speed
ELECTRIC HEATING
Type / Steps --- Wires / 1
Heating capacity kW 1.5 3.0
H e a t i n g --- m a x . c u r r e n t A 6 . 5
CABINET
Frame --- Galvanised steel
Painting --- Polyester --- RAL7035
OVERALL DIMENSIONS
Width / Height / Depth (HPSC outdoor unit) mm 920 / 840 / 390
Width / Height / Depth (HPSE indoor unit) mm 800 / 310 / 800
Weight (HPSC outdoor unit) kg 80 82
Weight (HPSE indoor unit) kg 50 53
Notes:
(1) – Indoor reference conditions: 30˚C / 35% R.H. air intake. Outdoor reference conditions: 35˚C. Nominal power supply.
(2) – Values referred to nominal speed (factory set).
(3) --- Measured with max. outdoor temperature at 2 m from the unit, in free field conditions.
(4) --- Maximum outdoor temperature referred to 30˚C / 35% R.H. air intake.