Compatibility With Other Emerson Products and Communication Protocols
3
Compatibility With Other Emerson Products and Communication Protocols
The Liebert IntelliSlot Web Card family, formerly the OpenComms line, includes:
The Web cards support the following protocols:
Liebert IntelliSlot Web cards support both 10Mbit and 100Mbit communication speeds and either
half or full duplex.
Table 1 Compatibility With Liebert equipment
Liebert IntelliSlot Card Part Number Compatible with:
Liebert IntelliSlot Web Card IS-WEBCARD
Liebert GXT
Liebert GXT 6kVA&10kVA
Liebert GXT3
Liebert GXT2U
Liebert Nfinity
®
Liebert PowerSure PSI
(prior to July 2008)
Liebert IntelliSlot Web Card-LB IS-WEBLB Liebert Hinet
Liebert NX
Liebert IntelliSlot Web Card-LBDS IS-WEBLBDS
Units with Liebert iCOM
®
Firmware prior to PA1.04.033.STD:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert DS
•Liebert XDF
Liebert IntelliSlot Web Card NXL IS-WEBNXL Liebert NXL
Liebert IntelliSlot Web Card-L
Liebert IntelliSlot Web Card-IPBML
Modbus IP / BACnet IP
IS-WEBL
IS-IPBML
Liebert APM
Liebert CRV
Liebert HPC
Liebert HPM
•Liebert XDP
with Liebert iCOM
Units with Liebert iCOM Firmware PA1.04.033.STD or later:
Liebert Challenger 3000
Liebert Challenger ITR
Liebert CW
Liebert Deluxe
System/3
Liebert DS
•Liebert PeX
•Liebert XDC
with
Liebert iCOM
Liebert IntelliSlot Web Card-S
Liebert IntelliSlot Web Card-IPBMS
Modbus IP
IS-WEBS
IS-IPBMS
Units with Velocity v4 control only:
•Liebert FDC
•Liebert FPC
Liebert PPC
Liebert RDC
Liebert IntelliSlot Web/485 Card
With Adapter
IS-WEBADPT
Liebert AC Power and Precision Cooling systems not equipped with
a Liebert IntelliSlot port
Table 2 Liebert IntelliSlot card communication protocols
Liebert IntelliSlot Card Part Number
Communication Protocol
SNMP
V1,V2C
SNMP
V3 HTTP HTTPS EMAIL SMS TELNET
MODBUS IP/
BAC
NET IP
L
IEBERT
PROTOCOL
Liebert IntelliSlot Web Card IS-WEBCARD ** ✔✔✔ ——
Liebert IntelliSlot Web Card-LB IS-WEBLB ✔✔✔ ——
Liebert IntelliSlot Web Card-LBDS IS-WEBLBDS —— ——
Liebert IntelliSlot Web Card NXL IS-WEBNXL ✔✔✔
Liebert IntelliSlot Web Card-L IS-WEBL ✔✔✔
Liebert IntelliSlot Web Card-S IS-WEBS ✔✔✔
Liebert IntelliSlot Web Card-IPBML
Modbus IP / BACnet IP
IS-IPBML ✔✔——
Both
Liebert IntelliSlot Web Card-IPBMS
Modbus IP
IS-IPBMS ✔✔——
****
Modbus
IP only
Liebert IntelliSlot Web/485 Card
With Adapter
IS-WEBADPT
✔✔
——
*** ***
* SNMP v3 available for Liebert GXT3 only
** Modbus IP only for IS-IPBMS
*** Liebert DataMate & Mini-Mate support BACnet IP only on IS-WEBADPT (Modbus IP is not available on these units).
NOTE
See online demonstrations of Web cards installed in Liebert equipment at:
http://demos.liebert.com

Table of Contents

Other manuals for Liebert IntelliSlot

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert IntelliSlot and is the answer not in the manual?

Liebert IntelliSlot Specifications

General IconGeneral
BrandLiebert
ModelIntelliSlot
CategoryNetwork Card
LanguageEnglish

Related product manuals