13
Ta b . 6 --- N o i s e l e v e l s
The following table indicates the overall sound pressure level at full load conditions, measured 1m from the unit, according to ISO 3774,
with an outdoor temperature of 35 ûC and referred to free field conditions.
Models
Total
sound level
Models
Total
sound level
Models
Total
sound level
[dB(A)]
[dB(A)]
[dB(A)]
CBH/SBH004 CLH/SLH004
CQH/SQH004 58
CBH/SBH006 CLH/SLH006
63
CQH/SQH006
CBH/SBH007
CLH/SLH007 64 CQH/SQH007
59
CBH/SBH204
70
CLH/SLH204
CQH/SQH204 58
CBH/SBH206 CLH/SLH206
63
CQH/SQH206
CBH/SBH207 CLH/SLH207 64 CQH/SQH207
59
CBH/SBH008 CLH/SLH008
CQH/SQH008 60
CBH/SBH011 72 CLH/SLH011
65
CQH/SQH011
CBH/SBH014 CLH/SLH014
CQH/SQH014 61
CBH/SBH016 73 CLH/SLH016
66
CQH/SQH016
Tab. 7 --- R 407C refrigerant and oil charge
Models: CBH 004 006 007 204 206 207 008 011 014 016
Refrigerant charge (each circuit) [ kg] 7.8 12.2 15.3 5.0 6.7 8.5 8.7 12.8 16.2 18.3
Oil charge (each circuit) [lt] 6.20 8.00 3.25 3.30 6.20 8.00
Models: CLH 004 006 007 204 206 207 008 011 014 016
Refrigerant charge (each circuit) [ kg] 7.8 14.8 15.2 5.0 7.9 8.4 8.7 15.4 17.4 18.3
Oil charge (each circuit) [lt] 6.20 8.00 3.25 3.30 6.20 8.00
Models: CQH 004 006 007 204 206 207 008 011 014 016
Refrigerant charge (each circuit) [ kg] 10.9 14.6 15.2 6.6 7.8 8.4 11.2 16.6 17.4 23.7
Oil charge (each circuit) [lt] 6.20 8.00 3.25 3.30 6.20 8.00
Models: SBH 004 006 007 204 206 207 008 011 014 016
Refrigerant charge (each circuit) [ kg] 7.8 12.2 16.3 5.0 6.7 9.0 8.7 12.8 17.2 18.3
Oil charge (each circuit) [lt] 6.20 8.00 3.25 3.30 6.20 8.00
Models: SLH 004 006 007 204 206 207 008 011 014 016
Refrigerant charge (each circuit) [ kg] 7.8 15.8 15.2 5.0 8.4 8.4 8.7 16.4 17.4 18.3
Oil charge (each circuit) [lt] 6.20 8.00 3.25 3.30 6.20 8.00
Models: SQH 004 006 007 204 206 207 008 011 014 016
Refrigerant charge (each circuit) [ kg] 10.9 14.6 15.2 6.6 7.8 8.4 11.2 16.6 17.4 23.7
Oil charge (each circuit) [lt] 6.20 8.00 3.25 3.30 6.20 8.00