14
Tab. 8 --- Pump set characteristics (opt.)
2 pole pump set, standard head pressure (data refers to each pump)
Models 004 006 007 204 206 207 008 011 014 016
C
B
H
Water flow
m
3
/h
6.83 9.42 11.36 6.83 9.27 11.53 13.35 18.39 22.20 28.36
CBH
Available head pressure
kPa
127 116 99 156 142 125 142 134 96 73
C
L
H
Water flow
m
3
/h
6.66 9.32 11.67 6.66 9.16 11.85 12.95 18.19 22.90 27.23
CLH
Available head pressure
kPa
129 116 96 157 142 124 143 135 94 90
C
Q
H
Water flow
m
3
/h
6.89 9.65 11.41 6.89 9.49 11.57 13.45 18.72 22.16 27.40
CQH
Available head pressure
kPa
127 114 98 156 141 125 140 132 96 87
Pump quantity
Nr.
1 2
Pump rotor model
---
12--- 129 12--- 136 20---128 20--- 134
Nominal motor power
kW
0.75 1.1 1.5 1.85
Noise level
(*)
dB(A)
58 63 65
Pump weight
kg
10.4 12.7 13.8 15.4
2 pole pump set, high head pressure (data refers to each pump)
Models 004 006 007 204 206 207 008 01 1 014 016
C
B
H
Water flow
m
3
/h
6.83 9.42 11.36 6.83 9.27 11.53 13.35 18.39 22.20 28.36
CBH
Available head pressure
kPa
169 156 140 198 182 166 167 184 151 170
C
L
H
Water flow
m
3
/h
6.66 9.32 11.67 6.66 9.16 11.85 12.95 18.19 22.90 27.23
CLH
Available head pressure
kPa
171 156 137 199 182 165 168 185 149 182
C
Q
H
Water flow
m
3
/h
6.89 9.65 11.41 6.89 9.49 11.57 13.45 18.72 22.16 27.40
CQH
Available head pressure
kPa
169 154 139 198 181 166 165 182 151 180
Pump quantity
Nr.
1 2
Pump rotor model
---
12--- 136 20--- 128 20--- 134 40---160/40
Nominal motor power
kW
1.1 1.5 1.85 4.0
Noise level
(*)
dB(A)
58 63 65 70
Pump weight
kg
12.7 13.8 15.4 42.0
2 pole pump set, standard head pressure (data refers to each pump)
Models 004 006 007 204 206 207 008 011 014 016
B
H
30% glycol/water mixture flow
m
3
/h
7.90 10.86 13.26 7.90 10.68 13.45 15.68 21.53 26.27 33.58
SBH
Available head pressure
kPa
93 93 63 135 130 101 64 90 17 16
L
H
30% glycol/water mixture flow
m
3
/h
7.64 10.93 13.51 7.64 10.77 13.71 15.12 21.67 26.83 32.09
SLH
Available head pressure
kPa
101 98 76 141 136 115 72 96 20 42
Q
H
30% glycol/water mixture flow
m
3
/h
7.93 11.20 13.11 7.93 11.01 13.29 15.75 22.07 25.75 32.48
SQH
Available head pressure
kPa
124 104 82 166 143 120 103 95 29 66
Pump quantity
Nr.
1 2
Pump rotor model
--- 12 ---136
20--- 128 12--136 20--- 128 20--- 134 40--- 160/40
Nominal motor power
kW
1.1 1.5 1.1 1.5 1.85 4.0
Noise level
(*)
dB(A)
58 63 58 63 65 70
Pump weight
kg
12.7 13.8 12.7 13.8 15.4 42.0
2 pole pump set, high head pressure (data refers to each pump)
Models 004 006 007 204 206 207 008 011 014 016
B
H
30% glycol/water mixture flow
m
3
/h
7.90 10.86 13.26 7.90 10.68 13.45 15.68 21.53 26.27 33.58
SBH
Available head pressure
kPa
228 210 165 270 247 203 162 174 108 158
L
H
30% glycol/water mixture flow
m
3
/h
7.64 10.93 13.51 7.64 10.77 13.71 15.12 21.67 26.83 32.09
SLH
Available head pressure
kPa
236 214 178 276 252 217 171 180 111 185
Q
H
30% glycol/water mixture flow
m
3
/h
7.93 11.20 13.11 7.93 11.01 13.29 15.75 22.07 25.75 32.48
SQH
Available head pressure
kPa
259 220 184 301 259 222 202 180 120 209
Pump quantity
Nr.
1 2
Pump rotor model
--- 32--- 160/30 40--- 160/40
40--- 200/75
Nominal motor power
kW
3.0 4.0 7.5
Noise level
(*)
dB(A)
66 70 74
Pump weight
kg
35 42 64
(*) According to ISO 3744