Setting the Compressor Time Delay Switch (#2)
Note: The Lightstat TME must be powered Off and On in order to “read” a
change of switch settings.
When this switch is set to OFF, the minimum On and Off time for any stage of
Heating or Cooling will be 3 minutes.
When set to ON, there will be no minimum On and Off time for any stage of
Heating or Cooling.
In either position, the Fan will continue to run for 45 seconds after the Heating
or Cooling stops; unless the Fan switch is set to ON, in which case the fan runs
continuously.
During Setback the Fan will revert to the Auto Mode.