Check tray data:
Left times of egg turning and time to the next egg turning:
When turning times (U14) ≠ 0, the left times of egg turning and time to the next egg turning will display alternatively.
When the accumulated times of egg turning ≥ U14, LCD will display “STOP”, there will be no egg turning.
Keeping depressed for 3 seconds will reset the accumulated times of egg turning and incubation day counter.
When turning times (U14) = 0, the egg turning will never stop. LCD will display time to the next egg turning.
Output R5 Control
R5 as periodical air exhaustion (U20 = 0)
When U22 arrives, R5 is energized.
When U24 arrives, R5 is de-energized.
R5 as periodical air exhaustion + temperature and humidity high limit protection (U20 = 1)
When there is no warning, exhaust air periodically.
If room temp. ≥ T11 + T25, or room humidity ≥ H20 + H26, R5 energized.
If room temp. ≤ T11 + T25 – T26, and room humidity ≤ H20 + H26 – H27, stop protection.
R5 as periodical air exhaust + temperature high limit protection (U20 = 2)
When there is no warning, exhaust air periodically.
If room temp. ≥ T11 + T25, R5 energized.
If room temp. ≤ T11 + T25 – T26, stop protection.
R5 as periodical air exhaust + humidity high limit protection (U20 = 3)
When there is no warning, exhaust air periodically.
If room humidity ≥ H20 + H26, R5 energized.
If room humidity ≤ H20 + H26 – H27, stop protection.
Output R4 Control
R4 as illumination control (U30 = 0)
Press to turn the lamp on/off. When the lamp is turned on, it will be off after U34 automatically.
Under this setting,
When door is opened, R4 will be energized for U34 time. When door is closed, R4 will be de-energized.
R4 as Temperature and humidity high limit protection (U30 = 1)
If room temp. ≥ T11 + T25, or room humidity ≥ H20 + H26, R4 energized.
If room temp. ≤ T11 + T25 – T26, and room humidity ≤ H20 + H26 – H27, stop protection.
R4 as Temperature high limit protection (U30 = 2)
If room temp. ≥ T11 + T25, R4 energized.
If room temp. ≤ T11 + T25 – T26, stop protection.
R4 as Humidity high limit protection (U30 = 3)
If room humidity ≥ H20 + H26, R4 energized.
If room humidity ≤ H20 + H26 – H27, stop protection.
Output R8 (R9) Control
R8 as alarm output (U40 = 0)
R8 will be energized when there is alarming. Alarming definition: see paragraph Alarm
R8 as Temperature and humidity high limit protection (U40 = 1)
If room temp. ≥ T11 + T25, or room humidity ≥ H20 + H26, R8 energized.
If room temp. ≤ T11 + T25 – T26, and room humidity ≤ H20 + H26 – H27, stop protection.
R8 as Temperature high limit protection (U40 = 2)
If room temp. ≥ T11 + T25, R8 energized.
If room temp. ≤ T11 + T25 – T26, stop protection.
R8 as Humidity high limit protection (U40 = 3)
If room humidity ≥ H20 + H26, R8 energized.
If room humidity ≤ H20 + H26 – H27, stop protection.
Alarm
Alarm temperature and humidity:
High temperature alarming, when room temp. ≥ T11 + T21.
Low temperature alarming, when room temp. ≤ T11 – T22
High humidity alarming, when room humidity ≥ H20 + H24.
Low humidity alarming, when room humidity ≤ H20 – H25
Alarm action
When there is alarm:
R8 energized (when U40 = 0).
Buzzing (could be stopped by any key press).
Display the reason table: