97
1) COURANT NOMINAL DE COURT-CIRCUIT, 5000 A SYMÉTRIQUES EFF. MAXIMUM, 220 V POUR 200 V TRIPHASÉ,
240 V POUR 200 V MONOPHASÉ, 480 V POUR 400 V TRIPHASÉ.
2) CONVIENT AUX CIRCUITS NON SUSCEPTIBLES DE DE DÉLIVRER PLUS DE 5000 AMPÉRES SYMÉTRIQUES EFF.
MAXIMUM, 220 V POUR 200 V TRIPHASÉ, 240 V POUR 200 V MONOPHASÉ, 480 V POUR 400 V TRIPHASÉ.
3) AVEC UNE PROTECTION PAR DES FUSIBLES CLASSE RK5 DE CALIBRE NOMINAL MAXIMAL DE V, A, VÉRIFIEZ LE
TABLEAU SUIVANT.
4) AVEC PROTECTION PAR DES FUSIBLES DE CALIBRE RK5, VÉRIFIEZ LE TABLEAU SUIVANT.
5) LA PROTECTION INTÉGRÉE CONTRE LES COURTS-CIRCUITS N'ASSURE PAS LA PROTECTION DE LA DÉRIVATION. LA
PROTECTION DE LA DÉRIVATION DOIT ÊTRE EXÉCUTÉE CONFORMÉMENT AU CODE CANADIEN DE L'ÉLECTRICITÉ,
PREMIÉRE PARTIE.
6) AVERTISSEMENT : RISQUE DU CHOC ÉLECTRIQUE. UNE TENSION DANGEREUSE PEUT ÊTRE PRÉSENTÉE JUSQU'À 5
MINUTES APRÉS AVOIR COUPÉ L'ALIMENTATION.
Class RK5, rated 600 V ac, 10 A, Interrupting
Current 200 kA
Class RK5, rated 600 V ac, 15 A, Interrupting
Current 200 kA
Class RK5, rated 600 V ac, 20 A, Interrupting
Current 200 kA
Maximum Branch Circuit Fuses
Class RK5, rated 300/600 V ac, 6 A,
Interrupting Current 200 kA
Class RK5, rated 300/600 V ac, 10 A,
Interrupting Current 200 kA
Class RK5, rated 300/600 V ac, 20 A,
Interrupting Current 200 kA
Class RK5, rated 300/600 V ac, 30 A,
Interrupting Current 200 kA
Class RK5, rated 300/600 V ac, 50 A,
Interrupting Current 200 kA