EasyManuals Logo

Lochinvar Crest 1.5 Service Manual

Lochinvar Crest 1.5
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
3 Troubleshooting (continued)
51
Service Manual
Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT DESCRIPTION CORRECTIVE ACTION
Outlet Temp
Shutdown
Outlet water temperature has exceeded the
maximum outlet water temperature.
Verify that the system is full of water and that all air
has been properly purged from the system.
Verify that the boiler is piped properly into the heating
system. Refer to Section 5 - Hydronic Piping of the
Crest Installation and Operation Manual
for the proper piping methods for the Crest boiler.
Check for voltage to the boiler pump motor on a call
for heat. If voltage is not present, check wiring back
to the pump relay. Replace the pump relay if
necessary.
If 120 VAC is present on a call for heat and the boiler
pump is not operating, replace the pump.
Watch Dog Error
The main control board has detected an
internal fault.
Replace the main control board.
Write EEProm
The main control board has detected an
internal fault.
Replace the main control board.
CRC Parameters
The main control board has detected an
internal fault.
Replace the main control board.
No Error Stored
The main control board has detected an
internal fault.
Press the RESET button on the SMART TOUCH
display panel.

Other manuals for Lochinvar Crest 1.5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lochinvar Crest 1.5 and is the answer not in the manual?

Lochinvar Crest 1.5 Specifications

General IconGeneral
BrandLochinvar
ModelCrest 1.5
CategoryBoiler
LanguageEnglish

Related product manuals