Installation Manual WTS3 Series II
M013610b.doc 4
SET UP : SWITCH SW3 SELECTION
S
ELECTION OF THE CURRENT RANGE
Select switch SW3-5 according to the following table to select the output current range 4 - 20 mA
or 0 - 20 mA :
SW3-5 Output signal range
ON
4 - 20 mA
OFF
0 - 20 mA
S
ELECTION OF ANALOG FILTER
The device provides for the possibility of choosing between two types of damping of mechanical
vibrations or electrical noise. Select the switch SW3-4 for the desired choice of the filtering of the
analog signal as shown in the following table :
SW3-4
Analog filter
ON
2 msec.
OFF
200 msec.
S
ELECTION OF COARSE AMPLIFICATION
It is possible choose from three fields of signal amplification of the load cells. Select the switch
SW3-1, 2, 3 for the choice of the desired range as indicated in the following table :
SW3-1
SW3-2
SW3-3
Input signal range
(Coarse amplification)
ON
OFF
OFF
From 0,4 to 3,1 mV/V of useful signal
OFF
ON
OFF
From 0,2 to 1,5 mV/V of useful signal
OFF
OFF
ON
Special versionCustomer application
ATTENTION :
Our technicians are available for any requests for customization of the card with
fields other than standard.
SW3-6 : not used.