Installation Manual WTS3 Series II
M013610b.doc 3
APPLICATION AND PRINCIPLE OF OPERATION
The module WTS3 is an amplifier for strain gage. This amplifier offers a simple and valid
procedure for calibration using rotary switches and trim-pots.
The supply voltage of the transducer is 10 Vdc with the possibility of connection to 4 or 6 wires.
With six-wire connection, making a correct compensation of the voltage drop on the connecting
cables, for a calibration easier and a higher accuracy.
The block diagram following from an indication of the structure of the conditioning module.
Note the simultaneous presence of voltage and current outputs 4-20mA ranges and 0-10 V. The
outputs and the power of the load cell are electrically isolated from the external 24 Vdc. This allows
the connection of several weighing systems to a data collection system (PLC or PC) using the
same power supply (+24 Vdc) shared with other devices without problems.
ELECTROMAGNETIC COMPATIBILITY (EMC)
WTS3 conditioner meets EEC 89/336 directive requirements.
Due to its plastic box it is sensible to radiated interferences generated by radio transmitters.
Installation suggestions :
Use earthed shielded cables. To improve shielding efficiency, both sides of the cable shield can
be connected to earth. This is permitted when low values of earth resistance are detected.
Install the board in a earthed metal box. If the board is placed into a metal cabinet with other
systems, further shields are not necessary.