EasyManuals Logo

Logic II Series User Manual

Logic II Series
11 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background image
Installation Manual WTS3 Series II
M013610b.doc 5
TERMINAL BOARD CONNECTIONS
P
OWER SUPPLY
Use a power cable, with suitable protection to the environment in which they are installed, with a
maximum section of 1.5 sqmm.
L
OAD CELLS
Load cell output is a low level signal (few millivolts); then it is necessary to use a good quality
shielded cables.
A 4 or 6 wires twisted pairs 100% shielded cables is recommended. Refer to enclosed drawing to
match the cable twisted pair correctly.
C
URRENT AND VOLTAGE OUTPUTS
Shielded cables should be used also for analog output connection to external devices.
The 0-10 Vdc and 4-20 mA outputs are galvanically isolated from the power supply (+24 Vdc and
negative Com24).
The negative output voltage (-Vout) is connected internally to the negative output current (-Iout).
Voltage and current outputs can be used at the same time to connect two different devices.
The current output is active and provides for a maximum load (impedance of the connected load)
of 500 ohms. This means that can also operate with an impedance of zero since the output is
virtually a current generator.
The output voltage is low power (voltage). Is allowed a maximum load of 2 mA (load impedance
equal to 5 Kohm) purely resistive.
The standard calibration range is from 0 to 10 V which corresponds to the 4-20 mA range
(calibration standard factory).
It is possible select the range 0-20 mA. In this case you must repeat the calibration procedure as
described later.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Logic II Series and is the answer not in the manual?

Logic II Series Specifications

General IconGeneral
BrandLogic
ModelII Series
CategoryTransmitter
LanguageEnglish