Inverter output short circuit.
ID:431 ~ 433
DC components of Inverter current
ABC three-phase exceed allowable
range.
ID:441 ~ 444
Aftercurrent of the inverter exceeds
allowable range.
ID:451 ~ 455
The Inverter detects that temperature
exceeds allowable range.
ID:461 ~ 466
Drastic variations in external
conditions of the inverter results in
positive and negative bus voltages
exceed allowable range.
ID:471 ~ 474
The inverter detects relay failure.
ID:481
Inverter phase lock is abnormal.
ID:482
Inverter soft start fails.
ID:483
Output lightning arrester is abnormal.
ID:485 ~ 486
The inverter detects that fans are
normal.
ID:491
Output power derating
ID:451 ~ 455
Check whether the cables of the
inverter temperature sensor are
connected or not.
ID:471 ~ 474
Check whether relays of the
inverter are normal or not, and
are conglutinated or not.
ID:483
Check whether the output
lightning arrester of the inverter is
connected normally or not, and
are damaged or not.
ID:485 ~ 486
Check whether the cables of
inverter fans are connected or
not, and are damaged or not.
Communication between inverter
chips is abnormal.
501 ~ 502: EEPROM
components have problems.
503: Main and auxiliary chips
work abnormally.
Abnormal
version
detection
Software version mismatch
Note: Please contact the local dealer or supplier if the recommended solution in the above table fails to help you.