iS7 Ethernet Option Manual
20
(2) Implicit Message
An Implicit Message is also called an I/O Message. This is the data
communicated between the Client (Originator) and Server (Target) with
Input Instance and Output Instance, at preset period. Class 1
connection will be implemented.
Supported range
Transport Type
Originator->Target: Point to Point
Target->Originator: Multicast
Transport Trigger: Cyclic
Configuration Connection: 1
Connection Tag: Not available
Priority
Originator->Target: Scheduled
Target->Originator: Scheduled
Configuration Data: Not available