iS7 Ethernet Option Manual
21
Input Instance
This is the data of Inverter status sent from Inverter to PLC or other
Client devices periodically.
Instance
Byte
Bit 7 Bit 6 Bit 5 Bit 4
Bit 3 Bit 2 Bit 1 Bit 0
70
0
Running
1
(Fwd)
Faulted
1 -
2 Speed Actual (Low Byte) – RPM unit (Note 1)
3 Speed Actual (High Byte) – RPM unit
71
0
At
Reference
Ref
From
Net
Ctrl
From
Net
Ready
Running
2 (Rev)
Running
1 (Fwd)
Warning
Faulted
1 Drive State
2 Speed Actual (Low Byte) – RPM unit
3 Speed Actual (High Byte) – RPM unit
110
0
Running1
(Fwd)
Faulted
1 -
2 Speed Actual (Low Byte) – Hz unit (Note 1)
3 Speed Actual (High Byte) – Hz unit
111
0
At
Reference
Ref
From
Net
Ctrl
From
Net
Ready
Running
2 (Rev)
Running
1 (Fwd)
Warning
Faulted
1
Drive State
2
Speed Actual (Low Byte) – Hz unit
3
Speed Actual (High Byte) – Hz unit
141
0
Status Parameter - 1 data (Low Byte)
1
Status Parameter - 1 data (Hi Byte)
142
0
Status Parameter - 1 data (Low Byte)
1
Status Parameter - 1 data (Hi Byte)
2
Status Parameter - 2 data (Low Byte)
3
Status Parameter - 2 data (Hi Byte)
143
0
Status Parameter - 1 data (Low Byte)
1
Status Parameter - 1 data (Hi Byte)