10. Advanced functions
10-3
SV-iC5
10.2 Jog operation
Group LED display Parameter name
Set
value
Min/Max
range
Factory
defaults
Unit
Function
group 1
F20 Jog frequency - 0/400 10.0 Hz
I/O group
I22
[Multi-function input
terminal P3 define]
4 0/24 2
Set the desired jog frequency in F20.
Select the terminal among the Multi-function input terminal P1 thru P5 to use for this setting.
If P3 is set for Jog operation, set I22 to 4 {Jog}.
Jog frequency can be set within the range of F21 - [Max frequency] and F22 – [Start frequency].
Jog operation overrides all other operations except Dwell operation. Therefore, if Jog frequency
command is entered in the middle of Multi-Step, Up-Down or 3-wire operation, operation is executed at
Jog frequency.
P3 (JOG)
Run
command(FX)
Frequency
F20
Voltage
Run
command
F12
P3
P1
P3
CM
FX : I20 = 0
JOG : I22=4