EasyManua.ls Logo

LS Industrial Systems SV008iC5-1 - Overload Warning and Trip

LS Industrial Systems SV008iC5-1
143 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12. Protective functions
12-2
SV-iC5
12.2 Overload Warning and trip
Overload warning
Group LED Display
Parameter Name
Set
value
Min/Max
setting
Factory
default
Unit
Function
group 1
F54
[Overload warning level]
-
30/150
150 %
F55
[Overload warning time]
-
0/30
10 Sec
I/O group
I54
[Multi-function output
terminal select]
5
0/17
12
I55
[Multi-function relay select]
5 17
Select one output terminal for this function between MO and 30AC.
If selecting MO as output terminal, set I54 to 5 {Overload : OL}.
F54 : Set the value as a percent of motor rated current.
Current [ %]
F51
F52
60 ETH trip time [ sec]
Current
Multi- function
output
F54
t : Overload
warning time
t t

Table of Contents