XGB Analog edition manual   
15 - 6 
 
 
 
 
< Figure 15.3 Temperature- time graph according to P coefficient > 
 
(c) Considering table 15.3, as P coefficient decreases, offset increases but overshoot decreases.   
 
(d) Generally, offset can’t be solved with only P control. In order to remove the offset, P control 
and I control is used together.   
 
(4) Proportional Integral Control (PI Control) 
 In I control,  it  yields the output  proportional  to  error  accumulated according to  time. And  the 
expression is as follows.    
 
               
 
 
 
(a) In the expression 15.2.9, Ti means the time takes for MV
i, 
output by I control, to be added into 
real output. 
 
(b) Generally, I control is used with P control. So the expression of PI control is as follows. 
 
        
 
 
 
(c)  In  the  above  heating  system,  the  simulation  results  are  as  shown  in  the  table  15.4  when 
proportional coefficient is 2.5 and integral time is 1.5s.   
 
 Edt
T
K
KEMVMVMV
i
P
PiP