Chapter 15 PID Function (Built-in function) 
 
15 - 45 
 
 
scope of water level sensor.   
 
 Output data type: 0 ~ 4000   
 - It converts the input 0 ~ 10V to digital value from 0 ~ 4000 and delivers it to basic unit.   
- In the case, the resolving power of digital value 1 is 10/4000 = 2.5mV 
 
 Filter process, averaging: disabled 
 - The example sets the input values in order that filter process and averaging are not 
available.   
- For more information about each function, refer to 12 Analog I/O Module.   
 
 
(3) D/A Output Module Parameter setting 
 
(a) Set the parameter of D/A output module(XBF-DV04A) that output MV to a drive.   
How to set them is as same as A/D input module. In the example, it is set as follows.   
 
 
 
 RUN CH: CH0 RUN   
 - In the example, MV is output as CH0 of D/A output module.   
 Output scope : 0 ~ 10V   
 Input data type: 0 ~ 4000