4) Example of PID Auto-tuning program 
The example of PID auto-tuning program is illustrated as Figure 15.21. 
 
 
< Figure 15.21 Auto-tuning example program > 
 
(a) Devices used   
  
It is always on, so it readily operates once PLC is RUN. 
It starts operation of CH0 of Slot 1 A/D input module. 
It starts operation of CH0 of Slot 2 D/A output module. 
PV entered to A/D input module. 
MV entered to D/A output module. 
Device to which PV is entered for LOOP 0 auto-tuning 
Device to which auto-tuning MV of LOOP 0 is output. 
Junction that is on once auto-tuning is complete. 
Junction that is on once auto-tuning has an error. 
Min. MV of auto-tuning designated in parameter. 
 
(b) Program explanation   
1) Since F0099(always on) is ON if PLC is converted form STOP to RUN, CH0 of A/D and D/A 
starts operating.   
2) At the moment, PV entered to CH0 is moved to K1875, the input device of PV and saved 
accordingly.   
3) Once M0000 junction is on, the auto-tuning of loop 0 starts.   
4) The auto-tuning MV of loop 0 that is output by PIDAT command is output to D/A output 
module by line 14 MOV command.