46265 Old Parameters
Enable/Disable
NOTE:
Changing system type, PT/CT ratio, Energy Output, Energy Digit Reset Count will reset the energy.
The address is used to enable/disable the showing of Old Parameter Screens.
Refer TABLE 11 (or TABLE 12) for Old parameter screens.
46189 Time Based
Datalog Interval
Selection
46191
Logging
Parameter Count
This value decides the number of parameters to be logged in time based
datalogging. The value ranges from 1 to 30.
46193-
46251
Datalog
Parameter
1 to 30
46253
Load Profile
Datalog Select
The address is used to start/stop Load Profile Datalogging.
0: Start Load Profile datalogging 1: Stop Load Profile datalogging
46255 Start Date of
Load Profile
Datalog
This value show the starting date for Load Profile datalog.
This address are read only.
This address is used to read and write the interval between consecutive time log
entries in minutes. Valid value range 1-60
These addresses are used to read and write the parameters to be logged in
time based logging. For valid values, refer TABLE 13.
Address Parameter Description