Lumiax MT6020 Pro - 8, Technical Data; 8.1 Electrical Parameters

Default Icon
33 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Charging Ratio(%)
Internal temperature()
60 62 64 66 68 70 72 74 76 78 80 82 84 86
58
0
10
20
30
40
50
60
70
80
Reduce Charging Mode
Recover charging from over temperature protection
90
100
*When the internal temperature exceeds 65℃, the mode of charging power reduction is
started, and the charging power decreases 10% for every 5℃ increase of internal temperature.
If the internal temperature is higher than 85℃, the controller will stop charging. But when the
temperature drops below 75℃, the controller will resume working at 70% of rated power.
When the internal temperature decreases by 5℃, the charging power increases by 10%. When
the internal temperature is lower than 60℃, the full power can be recovered.
Charging Ratio(%)
Internal temperature()
84 82 80 78 76 74 72 70 68 66 64 62 60 58
86
0
10
20
30
40
50
60
70
80
90
100
X-axis is the internal temperature, Y-axis is the charging ratio.
For example, the full charging power of the controller is 1000W, when the
temperature rises to 75 ℃, the charging ratio drops to 80%, which is 800W.
When the controller recovers after over temperature protection, when the
temperature drops to 70 ℃, the charging power recovers to 80%, which is 800W.